Standard Object Types Supported
Object Type
Supported
Objects
Dynamically
Creatable
Dynamically
Deletable
Optional
Properties
Supported
Writable
Properties
Analog Input
;
Reliability Out_of_Service
Analog Value ; Reliability
Present_Value
a,b
Out_of_Service
a
Object_Name
c
Binary Input ;
Reliability
Active_Text
Inactive_Text
Out_of_Service
Binary Value ;
Reliability
Active_Text
Inactive_Text
Present_Value
Out_of_Service
Device ;
Max_Master
Max_Info_frames
Object_Identifier
Object_name
Max_Master
Group
;
N/A N/A
Multi-state Value ;
Reliability
States_Text
Present_Value
d
Out_of_Service
d
a : Present_Value and Out_of_Service properties are writable for every AV objects except :
¾ PI Heating Demand (AV21)
¾ PI Cooling Demand (AV22)
b : Present_Value property for Room Temperature (AV7) and Room Humidity (AV10) is writable only if
Room Temp Override (BV8) is enabled and Room Humidity Override (BV11) is enabled respectively.
c : Object_Name property is writable for the following object only :
¾ Room Temperature (AV7)
d : Present_Value and Out_of_Service properties are writable for every MV objects except :
¾ Heating Valve Status (MV26)
¾ Cooling Valve Status (MV27)
¾ Fan Status (MV28)
¾ Effective Occupancy (MV33)
List of Proprietary Properties
Property name ID BACnet Data type Description
Major_Version 1000 CharacterString
The version number of the BACnet
communications module. This is the hardware
version number
MS/TP_Address 1001 Unsigned Display the MAC layer address of the module
MS/TP_Baud_Rate 1002 Unsigned
Display the communication baud rate of the
module
Sensor_Offset 1005 REAL
Display the temperature or humidity calibration
value. The range is –5.0 deg F to 5.0 deg F for a
temperature and –15% to 15% for humidity.